Authors | Amir Movahedi, Abolfazl Halvaei Niasar, Gevork B. Gharehpetian |
---|---|
Conference Title | 27th Iranian Conference on Electrical Engineering (ICEE 2019) |
Holding Date of Conference | May 2019 |
Event Place | Yazd, Iran |
Presented by | دانشگاه کاشان |
Page number | 1-5 |
Presentation | POSTER |
Conference Level | International Conferences |
Abstract
This paper presents the comparison of static synchronous series compensator (SSSC) and static synchronous compensator (STATCOM) performance on transient stability and low voltage ride through (LVRT) improvement of a multi-machine power system connected with wind farms. Also, power system stabilizers (PSSs) are installed on four synchronous machines. It is generally accepted that there is a threat to the stability of power systems with the penetration of wind farm. Therefore, in order to improve LVRT and transient stability in power system, the paper proposes using of PI controllers in wind farms and combination of the PSS and FACTS controllers. Also, In the present paper gravitational search algorithm (GSA) has been applied for controllers design.
tags: GSA, LVRT, SSSC, STATCOM, Wind farm