نویسندگان | ابوالفضل عظیمی,حامد هاشمی دزکی |
---|---|
نشریه | Sustainable Cities and Society |
شماره صفحات | 1 |
شماره مجلد | 96 |
ضریب تاثیر (IF) | ثبت نشده |
نوع مقاله | Full Paper |
تاریخ انتشار | 2023-09-01 |
رتبه نشریه | علمی - پژوهشی |
نوع نشریه | الکترونیکی |
کشور محل چاپ | ایران |
نمایه نشریه | SCOPUS ,JCR |
چکیده مقاله
Several solutions, such as fault current limiters (FCLs), have been utilized to mitigate the challenges of smart grids and ADNs’ protection schemes. However, less attention has been paid to simultaneously optimizing the protection coordination and power quality (PQ) concerns, incorporating the FCLs. There is a research gap in the literature in developing a method for optimal placement and impedance value of FCLs to optimize the speed of the protection systems, voltage sag energy index, and voltage sag duration. This research aims to fill such a research gap by proposing a new multi-objective optimization problem based on the optimum placement and impedance value of FCL. The proposed method is examined by implementing the distribution network of the IEEE 30-bus test system. MATLAB and DIgSILENT are linked online to simulate the protection of the smart grid and PQ voltage-based analyses and find the best solutions by the genetic algorithm (GA). The comparative analyses infer that a 13.13% improvement in criteria, e.g., operating time of relays, voltage sag energy, and voltage sag duration, is achieved by optimal placement of FCLs, beside other decision variables.
tags: Optimal placement and sizing of fault current limiters (FCLs) Power quality voltage-based objective Voltage sag energy index (VSEI) Optimal protection coordination Directional overcurrent relays (DOCRs) Microgrids (MGs)