| نویسندگان | سجاد توحیدی-هاشم اورعی-محمد رضا ذوالقدری-محسن رحیمی کلیشادی |
| تاریخ انتشار | 2015-11-01 |
| نوع نشریه | الکترونیکی |
| نمایه نشریه | ISI |
چکیده مقاله
The use of brushless doubly-fed induction generator has been recently proposed for wind turbines because of its variable
speed operation with fractional size converter without the need to brush and slip ring. This paper introduces a control
scheme to improve low voltage ride-through capability of doubly-fed induction generator considering grid code requirements.
The proposed control strategy is based on analysis of flux linkages and back electromotive forces and intends to
retain the control-winding current below the safety limit (typically 2 pu) during severe voltage dips. The time-domain simulations
validate effectiveness of the proposed scheme to protect the converter against failure as well as support reactive
power required by German grid code.